Feature
☆Input port cable monitoring with 4.7KQ EOLR
☆Monitoring power supply
☆Two indicators for fire and fault
☆Normally-open or Normally-close output automaticallyfollows
input port to change state
☆Electronically addressed.Addresses can be modified infield
☆Rail mount or surface mount
Technical Specifications
☆Operating Voltage (Loop): 24VDC(16VDC-28VDC)Power
Limited
☆Power Voltage: 24VDC(20VDC-28VDC)Power Limited
☆Standby Current:
≤0.26mA(Loop)
S18mA(Power)
☆Action Current:
≤0.39mA(Loop)
≤60mA(Power)
☆Output Capacity: 2A @ 30 VDC, 0.35PF
☆Voltage of input Port: 16.8VDC-27.6VDC
☆Input Capacity:
30 detectors or manual call points,
or 9 detectors with remote indicato!
☆Programming: Electronically addressing
☆Address Range: 1 address, from 1 to 242
☆Indicator:
Fire LED: RED, illuminates in fire conditionquiet when 24vDC
power is off and flashesin other states
Fault LED: Yellow, flashes 0.5s/on and
0.5s/off when input
fault
occurs.0.2s/on and 0.8s/off when ground fault occurs, quietin
other states.
☆Ingress Protection Rating: IP30 ( not tested by UL)
☆Operating Temperature: 0°C~+49°C
☆Relative Humidity: ≤ 93%, Non Condensing
☆Material and Color ofEnclosure: ABS, white (RAL9016)
☆Dimension (LxWxH): 85.3mmx78mmx33mm
☆Weight: About 74.1g
|