Feature
☆ Address can be programmed in field
☆ Strong environmental adaptability due to drift compensation
☆ Remote indicator output available
☆ Reed switch test
☆ Self-diagnostic
☆ Polling LED can be set to OFF
☆ 3 levels of smoke sensitivity programmable,
complying to UL268 7th Edition; Fixed temperature
feature complies to UL521
Technical Specifications
☆ Operating Voltage:loop 24V(16V-28V)
☆ Standby Current:≤0.4mA
☆ Alarm Current:
≤1.4mA (without remote indicator)
≤ 3.4mA (with remote indicator)
☆ Fire LED : Red.Flashes in polling, and illuminates in alarm
☆ Fault LED:Yellow.Illuminates steadily in fault
☆ Remote Indicator Output:
Polarity-sensitive output, directly connects to remote indicator (built in 10k resistor in series with max. output current 2mA); Flashes in alarming and does not illuminate in normal state.
☆ Programming Method:Electronically addressed
☆ Address Range:Occupying one address within 1~242
☆ Wiring:Loop:
two wire, polarity-insensitive Remote indicator: two-wire, polarity sensitive
☆ Smoke sensitivity Range:
Level 1: 1.38%~3.38%/ft
Level 2: 2.25%~4.25%/ft
Level 3: 3.12%~5.12%/ft
☆ Max. spacing (when used as heat detector only) :50 ft. (15.2 m)
☆ Action Temperature:135℉(57.2℃)
☆ UL Approved Environment Temperature:
32° F (0°C)~120° F (49°C)
0 - 95%, non condensing
☆ Operating Environment Temperature:
14° F (-10°C) ~122° F (+50°C)
0~95%, non-condensing
☆ Ingress Protection Rating:IP2X
☆ Dimensions:Diameter: 100mm Height: 54.5mm (with base)
☆ Mounting Hole Distance:45mm~75mm
☆ Weight:About 110g
|