Feature
☆Loop powered.
☆Optical Pathway 5 -100 Meters.
☆Maximum monitoring area: 14 x100=1400m2
Maximum width: 14m
☆Combination of the emitting and receiving part makes mounting easy and optical pathway accurate.
☆Built-in microprocessor enables intelligent judgment about fire alarm and fault.
☆Easy alignment and commissioning via supporting of onboard laser pointer and digital signal intensity indication.
☆Self-diagnostic function can monitor the internal fault.
☆Drift compensation for factors changing, such as a certain of dust accumulation, positional excursion, and ageing transmitter.
☆Electronically addressed by programmer.
☆Four sensitivity levels can be set in field.
☆LPCB Approved
Technical Specifications
☆Operating Voltage: 24VDC (16V~28V)
Commissioning current: ≤ 20mA
Standby current: ≤ 2mA
Alarm current: ≤ 5mA
☆Angle of Adjusting -6°to +6°
Maximum angular misalignment ±0.5°
☆Sensitivity Level:
Level 1: 1.3dB
Level 2: 1.8dB (factory default)
Level 3: 2.3dB
Level 4: 2.8dB
☆Operating Environment:
Temperature: -10°C - +50°C
Relative Humidity≤ 95%, non -condensing
☆Ingress Protection Rating:
IP20 without glue-seal
IP66 through glue-seal treatment
☆Material and Color of Enclosure: ABS, gray
☆Dimensions: 206mm X 95mm X 95mm
☆Weight: 450g
|