Feature
☆ Field-configurable switch for selecting the desired candela output.
☆ Field-configurable jumper for the strobe signal output.
☆ The candela output setting is locked in place and remains visible after final installation.
☆ This strobe features an enhanced synchronization circuit to comply with the latest requirements of UL 1971 Signaling Devices for the Hearing Impaired.
☆ Synchronized operation requires that you connect the DC-M9415 Series Wall Mount Strobe to a NAC output set for Synch Mode, or to a separate DC-M9410 Signal Synchronization Module.
☆ Designed for indoor use.
Technical Specifications
Operation Voltage
|
24 VDC or 24 VFWR nominal
|
Operation Current (under 16VDC)
|
|
|
Strobe (cd)
|
Operating current
|
|
15cd
|
0.103A
|
|
30cd
|
0.141A
|
|
75cd
|
0.255A
|
|
110cd
|
0.311A
|
Light Output
|
Selectable at 15, 30, 75 and 110 cd
|
Strobe signal rate
|
1 flash per second (fps)
|
Ingress Protection Rating
|
IP33
|
Operating Temperature
|
32 to 120°F (0 to 49°C)
|
Relative Humanity
|
0 to 93% noncondensing
|
Compatible electrical boxes
|
Single-gang box, 2-1/2 in. (64 mm) deep
|
Models
Model number
|
Description
|
DC-M9415R
|
Strobe, red
|
DC-M9415W
|
Strobe, white
|
|