DC-9202(IS) Intrinsically Safe Conventional Manual Call Point
 

Feature

    ☆Plug-in structure, easy for installation
    ☆The triggering glass is restorable using a special key after
        pressed


Technical Specifications

    ☆Operating Voltage: Loop 24VDC(16VDC~28VDC)
    ☆Operating Current: Standby Current: 0mA
                        Alarm Current: ≤30mA
    ☆Output Capacity: Volt-free normally open output contact
        signalrated 30VDC/100mA,contact resistance≤0.10Ω
    ☆Type of initiating Part: Reusable
    ☆Initiating Mode: Pressing the glass manually
    ☆Reset Mode: Reset by a special key
    ☆Fire Alarm indicator: Red. lt is off normally and illuminates
        underfire condition
    ☆Operating Environment: Type: indoor
                                              Temperature: -10°C~+55°C
                                             Relative Humiditys95%, non-condensing

 