DC-9101E Conventional Combination Heat Photoelectric Smoke Detector
 

 Features

    ☆ Drift compensation enables strong environmental adaptability
    ☆ Self-diagnostic
    ☆ Reed switch test
    ☆ Dirty chamber checking
    ☆ Fire LED allows 360° viewing
    ☆ Possible to switch off polling LED
    ☆ Remote indicator output
    ☆ 2 levels smoke sensitivities programmable
    ☆ Level 1 complies with EN 54-7. Heat part complies with EN
        54-5


Technical Specifications

    ☆ Operating Voltage: 24VDC (16VDC - 28VDC)
    ☆ Standby Current: ≤ 60μA
    ☆ Alarm Current: ≤ 55mA
    ☆ LED Indicator: Red, periodically flash once in polling when
        the status is set to “ON”; don’t illuminate when the status is set
        to “OFF”. Periodically flash twice in fault or sensing chamber
        dirty; illuminate in alarming
    ☆ Wiring: Polarized 2-core for Zone. Polarized 2-core for remote
        indicator
    ☆ Sensitivity Level: 2
    ☆ Alarm Reset: Instantaneous power down (Min. 2sn, Max.
        1.0VDC)
    ☆ Heat Detector Class: A2R
    ☆ Action Temperature: 62 °C
    ☆ Area coverage: Ceiling in open areas 80m2 (subject to local
        standard)
    ☆ Environment Temperature: -10°C ~ 50°C
    ☆ Relative Humidity: ≤95%, non-condensing
    ☆ Material of Enclosure: ABS
    ☆ Ingress Protection Rating: IP2X
    ☆ Dimensions: Diameter: 100mm Height: 54.5mm (with base)
    ☆ Mounting Hole Distance: 45mm ~ 75mm
    ☆ Weight: About 110g

 

Download:DC-9101E_DS10106284 Datasheet